A double-leaf masonry wall has an air cavity between the leaves that is doing very little thermal work, while mortar droppings bridge it and wall ties conduct through it. Cavity insulation fills that void with a fire-retarded EPS element that keys into the mortar courses, lifting the wall's thermal resistance and cutting HVAC load without changing the wall footprint or the bricklaying sequence. Important scope note: under SANS 10400-XA a double-skin (cavity) masonry wall is already DEEMED-TO-SATISFY, so this is not a compliance rescue for masonry — it is a performance upgrade (comfort, running cost, rational-design/energy-model route) and a compliance route only for lightweight or otherwise non-qualifying walls.
| Requirement | Target | Standard | Note |
|---|---|---|---|
| External wall — deemed-to-satisfy route | Double-skin (cavity) masonry, or a plastered single leaf >= 140 mm, satisfies the wall requirement as-built | SANS 10400-XA | No added insulation is REQUIRED on a masonry cavity wall to comply. Do not present PolyKey as a compliance necessity here — it is performance above the minimum, or an input to a rational-design / energy-model submission. |
| External wall — lightweight / non-qualifying construction | Minimum total R >= 0.35 m2K/W | SANS 10400-XA | This is the only wall R-value the standard actually mandates, and it applies to walls that do NOT qualify under the deemed-to-satisfy route (e.g. lightweight framed walls). Any EPS insulation layer clears it easily. |
| Roof / ceiling total R (context — a separate requirement) | 3.7 m2K/W in all zones; Zone 5 humid-coastal may use 2.7 m2K/W with roof ventilation | SANS 10400-XA:2021 | Cavity wall insulation does NOT contribute to the roof/ceiling R-value. XA:2011 was zone-specific (1:3.7, 2:3.2, 3:2.7, 4:3.7, 5:2.7, 6:3.5); confirm which edition the local authority is enforcing. |
| Reaction to fire of the EPS element | B-s1,d0 | SANS 53501-1 (Euroclass) | Reaction-to-fire only. It is NOT a fire-resistance (REI / minutes) rating, and no fire-resistance rating exists for the element — in this application it is encapsulated between two masonry leaves. All EPS is combustible (fire-retardant treated). |
Layers listed outside → inside.
The primary element for this application: interlocking fire-retarded FRCel EPS cavity insulation, T&G edges keying into the mortar courses of a double-leaf masonry wall, 340 x 1200 x 60/40 mm.
View product →
Plain cut-to-size FRCel EPS sheet as an alternative cavity fill where the interlocking PolyKey profile is not wanted, or where a non-standard cavity width must be filled.
View product →
Alternative wall system, not a cavity insert: the LiteCore Building System is the only Technopol product with an Agrement SA certificate (2020/609), and only as a NON-LOAD-BEARING wall. Consider where the design is not a traditional double-leaf masonry cavity wall.
View product →
Alternative route when the cavity is unavailable (solid or existing wall): a separate continuous external EPS layer on top-hat rails, weather-skinned with bare 0.5 mm roll-formed PPGL/PPGI LiteClad profiles. LiteClad is a steel weatherskin only — NOT a composite or insulated panel — and adds negligible R on its own.
View product →
| Property | Value | Standard | Source report | Status |
|---|---|---|---|---|
| Thermal conductivity (lambda, k @10 degC) | <= 0.035 W/m.K | EPS grade datasheet value for HD/20DV (20 kg/m3) | Technopol EPS grade datasheet — no PolyKey-specific test report exists | Provisional |
| Thermal resistance R of the 60/40 mm element (tested with wall ties) | 2.0 m2K/W | Guarded hot-box (report not named in the register) | 2025 guarded hot-box value, unnamed report — supersedes the conflicting older brochure R-tables (2023: 1.60@50 / 3.20@100 / 4.84@150; 2014/2017: 1.5@60), which must not be reprinted | Provisional |
| Nominal density / grade | 20 (HD / 20DV) kg/m3 | EPS grade datasheet | Technopol EPS grade datasheet / PolyKey brochure | Provisional |
| Compressive stress at 10% deformation | >= 110 kPa | EPS grade datasheet (grade-dependent, not a PolyKey-specific test) | Technopol EPS grade datasheet | Provisional |
| Element size (H x L x thickness, T&G profile) | 340 x 1200 x 60/40 mm | Product geometry | PolyKey brochure / spec table | Provisional |
| Reaction-to-fire classification (EPS FRCel 20DV, 60 mm) | B-s1,d0 | SANS 53501-1 (Euroclass) | IT 23-08-00009 (FIRELAB, issued 2023-08-04, valid to 2028-08-04) | Verified |
| Fire-resistance (REI) rating of the element | None — no fire-resistance rating exists for an EPS cavity element | SANS 10177-2 | No in-validity fire-resistance test covers this element; the wall's fire resistance comes from the masonry leaves, not the EPS | Provisional |
| Quality management system (company credential) | ISO 9001:2015 certified | ISO 9001:2015 | EQCSA Reg no. Q 2016024 (SANAS C22), valid to 2028-06-02 | Verified |
What these labels mean is defined on our data promise; every source report is on the register.
Enter the climatic zone and wall build-up. For a double-skin masonry wall it will confirm you are already deemed-to-satisfy; use it to see what cavity insulation buys you above the minimum, or to size a lightweight wall to the R >= 0.35 m2K/W floor. Then run ../../technical/thermal-bridge/ for the wall-tie psi-value before quoting any assembly U-value, and ../../technical/spec-writer/ for the clause text.